240kw factory supply diesel genset with Perkins 1606A-E93TAG5 engine

Prime 240kw 300kva factory supply diesel genset with Perkins 1606A-E93TAG5 engine for sale from China manufactory, coupled with original Stamford HCI444D alternator and original water cooled radiator, it consumes less diesel fuel and lube oil, and with the world's longest working time before first overhaul, with Perkins global service network, it is ideal for your backup or main electricity power source. Both open type ( within 105 DBA ) and silent type ( within 70 DBA ) Perkins 1606A-E93TAG5 diesel engine generator set in stock.

SKU: 240GF-P Category:
General Details

240kw factory supply diesel genset with Perkins 1606A-E93TAG5 engine overall specifications

Model: 240GF-P
Prime Power: 240KW/300KVA
Standby Power: 265KW/330KVA

Diesel Engine Specifications

Engine Model 1606A-E93TAG5
Engine Manufacturer Perkins UK
Cylinder quantity 6
Cylinder Arrangement In-line
Cycle 4
Aspiration Turbo charged
Bore x Stroke (mm x mm) 117×146
Displacement 9.3 L
Compression Ratio 17.2:1
Prime power / Speed (KW/RPM) 261kw/1500
Standby power/ Speed (KW/RPM) 287kw/1500
Governor type N.A.
Piston Speed N.A.
ElectropaK net engine power N.A.
Total Lubrication System Capacity (L) 36
Total Coolant Capacity (L) N.A.
Fuel Consumption at 100% load (L/hour) N.A.
Starter motor 24V
Alternator 24V
Minimum cranking speed N.A.

Alternator Specifications

Alternator model HCI444D
Alternator manufacturer STAMFORD
Exciter type Single bearing, Brushless, Self-excited
Rated output prime power 300KVA
Rated speed 1500 rpm
Rated frequency 50Hz
Number of phase 3
Rated voltage 400V (Available with custom requirements)
Power factor 0.8
Voltage regulation NL-FL ≤±1%
Insulation grade H
Protection grade IP23

Dimension & Weight

Opent Type Overall Size:L×W×H (mm) 3500×1500×2400 Silent Type Overall Size:L×W×H (mm) 4500×2600×3500
Open Type Weight (kg) 2200 Silen Type Weight (kg) 4000
Inquire this product